欢迎登录材料期刊网

材料期刊网

高级检索

介绍了通过测量暂态地电压来检测10 kV高压开关柜内部局部放电的基本原理及目前常用的检测仪器,分析了应用中存在的主要问题,并提出了改进方法。依据改进方法组建了便携式检测系统,包括双通道探头、高速采集卡及上位机处理软件等,实现了地电波波形的采集、显示、波形分析及信号时间差的确定。应用该系统进行局部放电源的定位,验证了该改进方法的有效性。

The principle of partial discharge of 10 kV Switchgear detected by transient earth voltage (TEV) method and common instruments were introduced, and some existing problems in application were analyzed, and an improved technique was proposed. A portable detection system including two-channel probes, data acquisition card and PC software, was established according to the improved method, which can realize the collection, display and analysis of the TEV waveform and the determination of time differ-ence of signal. It is proved that the improved detection system is effective to locate the partial discharge source.

参考文献

[1] 宋杲,崔景春,袁大陆.2004年高压开关设备运行统计分析[J].电力设备,2006(02):10-14.
[2] 印华,王勇,王谦.12 kV开关柜内部放电的分析与处理[J].高压电器,2006(05):395-396.
[3] 谌天亮.因受潮引起35kV开关柜事故的技术分析[J].四川电力技术,2011(04):67-68.
[4] 潘长明,刘刚,熊炬,董泉,王晓阳,袁斌.高压开关柜绝缘事故的分析及防范措施[J].高压电器,2011(07):90-93.
[5] 刘云鹏,王会斌,王娟,律方成.高压开关柜局部放电UHF在线监测系统的研究[J].高压电器,2009(01):15-17.
[6] 王俊波,章涛,李国伟.在线检测10kV开关柜局部放电方法研究[J].绝缘材料,2011(06):60-64.
[7] 畅晓鹏,郑文栋,钱勇,黄成军.高压开关柜局部放电检测定位技术的应用及改进[J].电工技术,2011(12):69-70.
[8] 乔进朝,王进锁,樊毅.开关柜非嵌入式局部放电在线检测定位研究[J].山西电力,2008(05):24-26.
[9] 陈刚.声电波检测仪在10kV开关柜局放检测中的应用[J].电工技术,2010(07):67-68.
[10] 骆洁艺 .基于暂态地电压和超声波测试的10kV开关柜绝缘状态评估技术的研究[D].广州:华南理工大学,2010.
[11] 杨献智,章坚.10kV配网开关柜局部放电带电检测应用[J].电力科学与工程,2011(06):71-75.
[12] Wagenaars P;Wouters PAAF;van der Wielen P et al.Ac-curate Estimation of the Time-of-arrival of Partial Dis-charge Pulses in Cable Systems in Service[J].IEEE Trans-actions on Dielectrics and Electrical Insulation,2008,15(04):1190-1199.