在容性设备绝缘在线监测中以PT二次电压信号作为相位参考存在不足,为了准确监测设备的绝缘状态,基于相对介损测量法,利用3δ准则通过相对介损历史监测数据来确定介损的正常变化范围,然后根据相对介损值变化向量确定故障台数,进而由故障诊断矩阵对单台或多台故障设备进行准确定位。最后通过实验室人工模拟实验验证了本方法的有效性。
In view of the deficiency when using PT secondary voltage signal as phase reference in online monitoring of capacitive equipment insulation and to monitor the insulation condition of equipment precisely, based on the relative measurement method, we determined the normal variation range of dielectric loss factor by historical monitoring data using 3δ criterion. The number of failure equipments was determined according to the change vector of dielectric loss factor, and then single or multiple faulure equipments were located precisely by fault diagnosis matrix. Finally, the effectiveness of the method was verified by artificial simulation experiment in laboratory.
参考文献
[1] | 史保壮.在线监测电容型设备绝缘方法研究[J].高电压技术,2002(04):24-25,59. |
[2] | 黄建华,金园,何青.电容型设备绝缘在线监测系统及其选用原则[J].高电压技术,2001(05):13-16,19. |
[3] | 王楠,陈志业,律方成.电容型设备绝缘在线监测与诊断技术综述[J].电网技术,2003(08):72-76. |
[4] | 徐志钮,律方成,姚辉,李和明.改进基波相位分离法在介损角测量中的应用[J].高电压技术,2007(05):29-31,49. |
[5] | 龚李伟,文远芳,侯镭.具有同时性综合相对测量法的应用[J].高电压技术,2005(08):36-38. |
[6] | 陈晓宇,李电.PT二次负载对绝缘在线监测系统的影响[J].高电压技术,1999(03):33-34. |
[7] | 陈安明,杨洋,黄文龙,许强,付祥波,张智勇.变压器油纸电容式套管介损试验及分析[J].绝缘材料,2013(03):80-82. |
- 下载量()
- 访问量()
- 您的评分:
-
10%
-
20%
-
30%
-
40%
-
50%