某核电站重要厂用水管道采用内壁涂层与阴极保护系统联合防护,一年多运行后,内壁部分区域防护层失效,对其失效处进行了分析.结果表明:阴极保护系统中多个参比电极故障导致其反馈信号错误,造成过保护使防护层失效.通过2种方法对现有阴极保护系统进行评估,认为防护层应有计划地予以维护,保证破损率维持在30%以下,才能保证管道始终处于保护状态.
参考文献
[1] | Stephen D C.ASM Handbook Vol.13B:Corrosion:Materials[M].Nevada:ASM International,2005:672. |
[2] | BS 7361-1.Cathodic protection Part 1:Code of practice for land and marine applications[S]. |
[3] | Armstrong R D;Johnson B W;Wright J D .An investigation into the cathodic disbondment of epoxy-polyamine protective coatings[J].Electrochimica Acta,1991,36:1915-1923. |
[4] | Baeckmann W V;赖敬文.阴极保护简明手册[M].北京:石油工业出版社,1987:123-126. |
[5] | GJB 156A.港工设施牺牲阳极保护设计和安装[S]. |
[6] | McGrath J N;TigheFord D J .Time-dependent development of cathodic protection within pipes and its modeling[J].Corrosion,1984,40(11):604-605. |