基于以氯化锂水溶液为除湿剂的除湿冷却系统(DECS),对其溶液的再生过程进行实验研究.研究了热源温度、溶液浓度对填料塔式再生系统再生性能的影响情况,实验表明溶液浓度在20%时,空气含湿量最大增量为37.1 g/kg干空气.计算出几种工况下的传质系数,最大的传质系数为0.0072 kg/(m2·s),并得出系统有关参数对传质系数的影响,为此类再生器的性能模拟与设计提供关键性的数据.