双级压缩跨临界CO_2热泵适合于低温地板辐射采暖.以北京市某建筑为对象,进行了双级压缩跨临界CO_2热泵中间冷却型式的优化分析.结果表明:与单级压缩循环相比,双级压缩循环提高了系统供热的性能系数(COP),并且双级压缩循环中间完全冷却的COP高于中间不完全冷却型式.同时在保持最佳中间冷却压力下,双级压缩中间不完全冷却型式的COP随着高压级压缩机入口CO_2蒸气过热度的增加而逐渐减小.因此在实际系统设计中,双级压缩跨临界CO_2采暖热泵宜采用中间完全冷却型式.
A two-stage trans-critical CO_2 heat pump is suitable for heating low-temperature radiant floor.For an architecture in Beijing,the intercooling pattern optimization of a two-stage trans-critical CO_2 heat pump is processed.Results indicate that the two-stage compression cycle has a higher coefficient of heating performance(COP)than that in a single stage compression cycle.For a two-stage compression cycle,the COP of a complete intercooling type is higher than an incomplete intercooling type.As the degree of superheated CO_2 vapor at higher stage compressor inlet increases,the COP of the incomplete intercooling type decreases under the optimum intermediate pressure.So when designing the actual system,the intercooling pattern of a two-stage trans-critical carbon dioxide heat pump should be a complete type.
参考文献
[1] | 马一太,王景刚,魏东.自然工质在制冷空调领域里的应用分析[J].制冷学报,2002(01):1-5. |
[2] | 王景刚.CO2跨临界双级压缩带膨胀机制冷循环研究[J].制冷学报,2001(02):6. |
[3] | Sarkar J;Bhattacharyya S;Ramgopal M .Optimization of Transcritical CO_2 Heat Pump Cycle for Simultaneous Cooling and Heating Applications[J].International Journal of Refrigeration-Revue Internationale du Froid,2004,27(08):830-838. |
[4] | 李敏霞,马一太,安青松,苏维诚.CO2跨临界循环水源热泵的封闭式摆动转子膨胀机[J].机械工程学报,2008(05):160-164. |
[5] | 王景刚.CO2跨临界双级压缩带膨胀机制冷循环研究[J].制冷学报,2001(02):6. |
[6] | Robinson D M;Groll E A .Eficiencies of Transcfitical CO_2 Cycles with and Without and Expansion Turbine[J].Journal of Refrigeration,1998,21(07):577-589. |
[7] | 李敏霞,李丽新,苏维诚,马一太.二氧化碳跨临界循环带膨胀机热泵系统的实验研究[J].工程热物理学报,2004(06):929-931. |
[8] | 马一太,洪芳军,王景刚,苏维诚.CO2跨临界双级压缩采暖热泵理论分析[J].大连理工大学学报,2001(z1):S5-S8. |