本文在固体除湿换热器的基础上提出了一个新型太阳能驱动的连续除湿换热器(CSCHE)空调系统,并建立了与之相对的实验平台,本系统通过对两个除湿换热器(SCHE)内的再生热水和冷却水进行切换实现连续除湿的目的.在上海地区夏季典型工况下对除湿空调系统的设计可行性和除湿能力进行了验证,结果显示CSCHE空调系统的平均除湿量和系统的热力学系能系数(COPth)分别可以达到5.08 g/kg和0.34.
参考文献
[1] | 江泽民.对中国能源问题的思考[J].上海交通大学学报,2008(03):345-359. |
[2] | 江亿.我国建筑耗能状况及有效的节能途径[J].暖通空调,2005(05):30-40. |
[3] | Chung TW.;Chung CC. .Increase in the amount of adsorption on modified silica gel by using neutron flux irradiation[J].Chemical Engineering Science,1998(16):2967-2972. |
[4] | KAZUHISA YANO;YOSHIAKI FUKUSHIMA .Synthesis of Super-Microporous Aluminosilicate Having Excellent Water Vapor Adsorption Property as an Adsorbent for an Adsorption Heat-Pump[J].Journal of porous materials,2003(4):223-229. |
[5] | 钟金华 .陶瓷转芯复合干燥剂转轮实验研究[D].上海交通大学,2005. |
[6] | C. J. Simonson;R. W. Besant .Heat and moisture transfer in energy wheels during sorption, condensation, and frosting conditions[J].Journal of heat transfer: Transactions of the ASME,1998(3):699-708. |
[7] | Experimental comparison and analysis on silica gel and polymer coated fin-tube heat exchangers[J].Energy,2010(7):P.2893. |