欢迎登录材料期刊网

材料期刊网

高级检索

以水为冷却介质,对半实心旋流式机械雾化喷嘴的雾化性能及"无沸腾"区换热性能进行实验研究.PDPA的测试结果表明,该喷嘴在喷雾区有一明显的液滴速度、液滴直径减小的回流区,且距喷口越近,回流越明显.对质量通量为11.67~29.06 kg/(m2s)之间的换热性能研究发现,热流、换热系数均随着流量通量的增加而增强;壁面温度对"无沸腾"区换热亦有一定的影响,且壁面温度愈高,换热性能亦愈强.给出了反映壁面温度影响的无量纲参数§,并对Reynolds数为116.2~289.2的实验数据进行拟合得到反映"无沸腾"区换热特性的无量纲关系式.

参考文献

[1] Eric A. Silk;Eric L. Golliher;R. Paneer Selvam .Spray cooling heat transfer: Technology overview and assessment of future challenges for micro-gravity application[J].Energy conversion & management,2008(3):453-468.
[2] J. Yang;L. C. Chow;M. R. Pais .Nucleate boiling heat transfer in spray cooling[J].Journal of heat transfer: Transactions of the ASME,1996(3):668-671.
[3] I. Mudawar;K. A. Estes .Optimizing and predicting CHF in spray cooling of a square surface[J].Journal of heat transfer: Transactions of the ASME,1996(3):672-679.
[4] Lanchao Lin;Rengasamy Ponnappan .Heat transfer characteristics of spray cooling in a closed loop[J].International Journal of Heat and Mass Transfer,2003(20):3737-3746.
[5] Karwa N;Kale SR;Subbarao PMV .Experimental study of non-boiling heat transfer from a horizontal surface by water sprays[J].Experimental Thermal and Fluid Science: International Journal of Experimental Heat Transfer, Thermodynamics, and Fluid Mechanics,2007(2):571-579.
上一张 下一张
上一张 下一张
计量
  • 下载量()
  • 访问量()
文章评分
  • 您的评分:
  • 1
    0%
  • 2
    0%
  • 3
    0%
  • 4
    0%
  • 5
    0%